13 User modes
FLUXUS WD
13.1 StandardUser mode
103
UMFLUXUS_WDV1-3EN, 2018-07-16
NoiseTrek mode
If the proportion of gas or solid particles is high, the transmitter can toggle to the NoiseTrek mode.
• Select the menu item
Special settings
in the program branch
Options
.
• Press ENTER until the menu item
Enable NoiseTrek
is displayed.
• Select
Default
if no user-defined inputs are to be made.
• Select
On
to enable the NoiseTrek mode or
Off
to disable it.
• Press ENTER.
In order to manually toggle between the TransitTime and the NoiseTrek mode during the measurement, press key
when the measured value is displayed.
HybridTrek mode
The HybridTrek mode combines the TransitTime and the NoiseTrek mode. During a measurement in the HybridTrek
mode, the transmitter automatically toggles between the TransitTime and the NoiseTrek mode depending on the gaseous
or solid content in the fluid in order to receive valid measuring values.
If the NoiseTrek mode is enabled, the menu item
HybridTrek
will be displayed.
• Select
On
to activate the automatic toggling between the TransitTime and the NoiseTrek mode. If
On
is selected, the
NoiseTrek mode can also be activated and deactivated manually during the measurement.
• Select
Off
to deactivate the automatic toggling between the TransitTime and the NoiseTrek mode. If
Off
is selected,
the NoiseTrek mode can only be manually activated and deactivated during the measurement.
• Press ENTER.
If the automatic toggling between the TransitTime and NoiseTrek mode is activated, further parameters have to be config-
ured.
• Enter the time after which the transmitter has to toggle to the NoiseTrek mode if there are no valid measured values in
the TransitTime mode.
• Press ENTER.
• Enter the time after which the transmitter has to toggle from the NoiseTrek mode to the TransitTime mode if there are no
valid measured values.
• Press ENTER.
If there are valid measured values in the NoiseTrek mode, the transmitter can periodically toggle to the TransitTime mode
in order to check whether a measurement in the TransitTime mode is possible again. The time interval and the duration of
the checking are set as follows:
• Enter the time after which the transmitter has to toggle to the TransitTime mode. If zero is entered, the transmitter does
not toggle to the TransitTime mode.
• Press ENTER.
Notice!
Due to its higher measuring accuracy, the TransitTime mode should be used preferentially over the NoiseTrek mode.
Options\Special settings\Enable NoiseTrek
Options\Special settings\HybridTrek
Options\Special settings\HybridTrek\TT -> NT
Options\Special settings\HybridTrek\NT -> TT
Options\Special settings\HybridTrek\NT -> TT possible
Summary of Contents for FLUXUS WD
Page 1: ...FLUXUS WD UMFLUXUS_WDV1 3EN Operating instruction...
Page 6: ...Table of contents FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 6...
Page 150: ...18 Settings 18 9 Key lock FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 150...
Page 172: ...Annex D Conformity declarations FLUXUS WD 2018 07 16 UMFLUXUS_WDV1 3EN 172...
Page 173: ......
Page 174: ......