6.11.3 Operating mode
Only Cooling
(2-pipe system)
*)
set jumper terminals 13, 14 on-site
**)
Fan control (terminal diagram depending on selected rotational speed combination, see wiring diagram in the electric switch cabinet.
***)
Signal contact condensate pump fault (for wiring on further units, refer to wiring diagram chapter 6.11.1).
****)
In case of a condensate pump fault, the switch is automatically disconnected from the power supply.
Fig. 6-63: Fan and valve control
(unit with terminal strip)
Configuration
Fig. 6-64: Fan and valve control
(unit with terminal strip and condensate pump)
Fig. 6-65: Fan and valve control
(unit with relay PCB)
Fig. 6-66: Fan and valve control
(unit with relay PCB and condensate pump)
CET.ACEC
Unit with terminal strip
Parameter 3: SEL0 = 14 and SEL2 = auto
(2-pipe system)
Parameter 4: SEL0 = 16 and SEL2 = OFF
(fan On/Off)
Parameter 5: SEL0 = 18 and SEL2 = auto
Parameter 7: SEL0 = 22 and SEL2 = auto
Parameter 8: SEL0 = 24 and SEL2 = 2
(without sensor)
Parameter 9: SEL0 = 26 and SEL2 = auto
(centrally or via sensor)
CET.ACEC
Unit with terminal strip and condensate pump
CET.ACEC
Unit with relay PCB
CET.ACEC
Unit with relay PCB and condensate pump