Mounting
HyPower-Geko
30
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
4.4
Unit mounting
4.4.1 Installation with various fixing materials
To fasten the units, assembly mountings with 2 holes are provided (1 on each side, see
fig. 4-6, Pos. 1). Appropriate fixing accessories are needed depending on the mounting
variant (refer to fig. 4-5).
For mounting on the room ceiling, at least 2 holes (intake/discharge plenum, 1 on each
side) or 4 holes (basic unit or intake/discharge sound attenuator, 2 on each side) are
required.
The position of the holes of the assembly mountings is presented in thefig. 4-4. The
spacing of the holes of the assembly mountings correspond exactly to the spacing of
the assembly holes in the room ceiling, for the basic unit as well as the assemblies of
the accessory.
Risk of damage to the unit!
The unit must be mounted in such a way to ensure unobstructed air flow in subse-
quent operation.
The clearance between unit top line and the room ceiling should amount to at least
50 mm.
Fig. 4-4:
Hole spacing of the assembly mountings
Pos. 1:
Basic unit
Pos. 2:
Fan chamber
Pos. 3:
Discharge transition piece
Pos. 4:
Intake/discharge sound attenuator
Pos. 5:
Intake/discharge plenum
Model size
1
2
3
4
b [mm]
560
865
1170
1590
Tab. 4-4:
Unit size dependent width of accessories