Maintenance and Troubleshooting
FläktGroup DC-2014-0022-GB 2018-05/R5 • Subject to modifications
123
Pos. 1: Cover panel Fan room
Pos. 2:
Fastening screws (2
per side)
Pos. 3:
Filter panel
Pos. 4: Fan
•
Mount all components in the reverse order
8.3.7 Check internal insulation for dirt and mould and, if necessary, clean and disinfect
•
Shut off all medium supply of unit.
Fig. 8-7:
Check fan
User instructions!
Do not mount components in case of a subsequent check of fans!
Risk of personal injury!
Always wear protective gloves to prevent injury caused by sharp edges!
Damage to the unit!
It is prohibited to treat all surfaces with cleaning agents and disinfectants containing
organic acids, e.g. vinegar, formic acid or materials containing aldehyde (e.g. cin-
namic aldehyde). This can lead to corrosion. As a consequence unpleasant odours
may occur.
Disinfectant
Substance group
Manufacturer
Application concentration
Terralin protect
Glycol derivative, quaternary
compound
Schülke & Mayr GmbH
0.5 %
Incidin plus
Alkylamine derivative
Ecolab Deutschland GmbH
1 %
Preferably use "Terralin protect". The second choice is "Incidin plus"
Tab. 8-2:
List of disinfectants authorized by FläktGroup
Damage to the unit!
Protect electrical devices and furniture from escaping splash water!