5
Commissioning and in operation
62
Festo – GDCP-CMMS-AS-G2-FW-EN – 1310NH – English
5.7.5
Configure terminating resistor
The DIP switch [S1.12] may only be used for activating the “CAN bus” terminating resist-
or.
Fieldbus
Note
DIP switch
S1.12
CANopen
ON: terminating resistor active.
OFF: terminating resistor not active.
OFF/ON
DriveBus
PROFIBUS DP
In the PROFIBUS DP, the terminating resistor is
integrated into the “CAMC-PB” interface module.
OFF
DeviceNet
Terminating resistor can be connected externally,
if needed.
OFF
RS485
OFF
Tab. 5.8
Configure terminating resistor