INSTALLATION - DOOR CONFIGURATION
48
Installation guide
,
Sensors
Opening safety
sensors (SIO)
The safety
sensors
installed must
have a test
input to
monitor correct
operation. The
door switches
to MANUAL
MODE in the
event of test
failure.
Configuration The door stops if the safety device is enabled during opening. If disabled, the
door opens completely at slow speed or until a new safety activation. The
door continues to close if the opening safety device is enabled during
closing.
NC with no test
Normally closed with no test signal.
NC with test
Normally closed with test signal.
NO with test
Normally open with test signal.
Disabled
(default value)
Safety sensor in opening disabled.
Disable (30 to 90º, default value:
90
)
Opening safety sensor invalidation distance: prevents the
leaf from stopping due to the wall being detected.
Parameters curve
Closing
(see closing movement
diagram, page 50)
Speed (5 to 10 sec, default
value:
7
)
Increasing the value decreases closing movement speed
with motor. (KI, KA and KB activation).
Courtesy Speed (6 to 10 sec,
default value:
10
)
Increasing the value decreases closing movement speed
with motor. (Courtesy activation).
Slow Speed (1 to 5, default value:
3
)
Door speed in anti-crushing movement.
Acceleration (0 to 5, default
value:
1
)
Increasing the value increases initial opening movement
with motor acceleration.
Meeting position (5 to 30º,
default value:
5
)
Meeting final speed start distance.
Meeting Speed (1 to 5, default
value:
2
)
Increasing the value increases final meeting speed.
Opening
(see opening movement
diagram, page 50)
Speed (3 to 10 sec, default value:
5
)
Increasing the value decreases opening movement speed.
(KI, KA and KB activation).
Courtesy Speed (6 to 10 sec,
default value:
7
)
Increasing the value decreases opening movement speed.
(Courtesy activation).
Slow Speed (1 to 5, default value:
3
)
Door speed in anti-crushing movement.
Acceleration (0 to 5, default
value:
3
)
Increasing the value increases initial opening movement
acceleration.
Meeting Pos. (70 to 85º, default
value:
80
)
Meeting final speed start distance.
Meeting Speed (1 to 5, default
value:
3
)
Increasing the value increases final meeting speed.
Reverse
Quick reverse position (10 to 45º,
default value:
30
)
Position the door reverses quickly from.
Slow reverse position (60 to 80º,
default value:
70
)
Position the door reverses slowly from.