Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
51
00-02-0939
2019-06-13
13 = Reserved
Reserved
14 = Reserved
Reserved
15 = Remote Stop SD
(0 or 1)
40009
Read Only
Active Shutdown Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Coolant Level SD
(0 or 1)
1 = High Level SD
(0 or 1)
2 = Low Level SD
(0 or 1)
3 = High Flow SD
(0 or 1)
4 = Low Flow SD
(0 or 1)
5 = Reserved
Reserved
6 = Reserved
Reserved
7 = Water in Fuel SD
(0 or 1)
8 = Low Suction SD
(0 or 1)
9 = High Suction SD
(0 or 1)
10 = Reserved
Reserved
11 = High Engine Oil Temp SD
(0 or 1)
12 = Low Gear Box Pressure SD
(0 or 1)
13 = High Gear Box Pressure SD
(0 or 1)
14 = Reserved
Reserved
15 = Red Lamp Status
(0 or 1)
40010
Read Only
Active Shutdown Status (Active Fault: Bit = 1, Inactive: Bit = 0)
0 = Pivot Alignment SD
(0 or 1)
1 = INDEX Coolant Level SD
Reserved
2 = Speed Signal Lost While Running SD
Reserved
3 = Reserved
Reserved
4 = Reserved
Reserved
5 = Reserved
Reserved
6 = Reserved
Reserved
7 = Reserved
Reserved
8 = Reserved
Reserved
9 = Reserved
Reserved
10 = Reserved
Reserved
11 = Reserved
Reserved
12 = Reserved
Reserved
13 = Reserved
Reserved
14 = Reserved
Reserved
15 = Reserved
Reserved
40011
Read Only
Actual System Level (50.5ft will read 505)
Feet
40012
Read & Write Modbus Engine Start/Stop Auto Mode Only (Stop = 0, Start = 1)
(0 or 1)
40013
Read & Write Maximum Engine Speed Setpoint
RPM
40014
Read Only
Actual Ambient Temp
Celsius
40015
Read & Write Auto/Manual Mode (Manual = 0, Auto = 1)
(0 or 1)
40016
Read & Write Running Loaded Speed in Auto Setpoint
RPM
40017
Read & Write Manual Only (Manual Only Enabled = 1, Disabled = 0)
(0 or 1)
40018
Read & Write Prestart 1 Auto Only
(Prestart Auto Only = 1, Prestart Auto & Manual = 0)
(0 or 1)
40019
Read & Write Prestart 2 Auto Only
(Prestart Auto Only = 1, Prestart Auto & Manual = 0)
(0 or 1)