Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
18
00-02-0939
2019-06-13
J1939 Electronic Engine Setup (Factory Default)
1. Access
Menu/Engine Settings/Engine Type
to ensure J1939 is selected.
2. Press down arrow to
Engine Manufacturer
, select which engine manufacturer the controller is/will be
used then press
[Enter]
.
3. Press down arrow to
Engine Emission
, select the emissions level of the engine then press
[Enter]
.
4. Press down arrow to
Tier 4
(if a Tier 4 selection is made in Engine Emission menu), press
[Enter].
a. Press down arrow to
DEF Gauge
. Select Yes to show this gauge (if needed) then press
[Enter]
.
b. Press down arrow to
Percent Soot Gauge
. Select Yes to show this gauge (if needed) then
press
[Enter]
.
c. Press down arrow to
Regen Screen
. Select Yes to show this screen (if desired) then press
[Enter]
.
5. Press the
[Back]
key and down arrow to
Speed Source
, ensure J1939 is selected for CANbus engine
speed from ECU.
6. Press the
[Back]
key and down arrow to
Advanced Engine Settings
, and press
[Enter]
.
7. Ensure
Address Claim
is set to the CAN address that the TSC1 and Tier 4 regeneration is expected
to be sent from to the engine ECU (this is often times designated by the manufacturer/distributor).
8. Press down arrow to
Warnings and Shutdowns
, press
[Enter]
.
9. Ensure all warnings and shutdowns are below or above ECU settings if required to have the ECU
shutdown the engine instead of the MPC-10 / TEC-10 (for engine faults such as oil pressure and
coolant temperature).
NOTE:
If requiring the engine ECU to shutdown the engine on any engine shutdown
fault without help from the controller, select ECU Shutdowns in the System Menu and
change the setting to ECU Only.
10. Press the
[Back]
key and down arrow to
Throttle
, ensure desired throttle method is selected then
press
[Enter]
.
11. Press the
[Back]
key and down arrow to
Input/Output
, and press
[Enter]
.
12. Press down arrow to access
Analog Inputs,
ensure the analog inputs aren't set to oil pressure or
coolant temp (disable or change to something different).
13. Press down arrow to
Relay1-3 or DO1-4
, and assign desired outputs for Crank, ECU Enable and
Inc/Dec outputs if throttle type selected was Inc/Dec.
14. Press the
[Menu]
key to exit the menu setup screens.
Setting to Auto Start on a Single Contact Input (Single Float)
1. Access
Menu/Application Configuration.
Press the down arrow to
Auto Start/Stop Function
then press
[Enter]
.
2. Utilize the Up and Down arrows to select
Single Contact
then press
[Enter]
.
3. Press
[Back]
once, and select
Input / Output
then press
[Enter]
.
4. Press
[Enter]
to access
Digital Inputs
then assign the
Function
of
Single Contact Start/Stop
to one of the Digital Inputs.
5. Ensure no other Digital Inputs are set to a start/stop type.
6. Press the
[Menu]