Separate TSC1 Source Address
(High Security): allows the user to set a separate source address for
TSC1 th
rottling from the controller’s claim address. This should only be done if the service technician
knows this to be true.
Factory set to Disabled.
TSC1 Source Address
(High Security): allows setting TSC1 throttle to be sent from a source address
separate than the controller claim address. (Only appears when Separate TSC1 Source Address is set to
Enabled).
Target RPM Step Size
(Medium Security)
: t
his is the step size of the target RPM when increasing and
decreasing. The actual rate of change is much higher when throttling in auto vs. manually with the push
buttons.
Factory set to 25 RPM.
Throttle Deadband RPM
(Medium Security)
:
format of # RPM. Plus/minus value added to the target to
provide a range of RPM during which the throttle is not active. No throttling will occur when the engine
RPM is within the RPM deadband.
Factory set to 25 RPM.
(Only appears when Pulse Inc/Dec is chosen
for the Throttle Type)
Throttle Inc/Dec Pulse
(High Security)
:
format of # mS. The amount of time to pulse the throttle. Increase
this value for faster engine response, or decrease this value for slower engine response.
Factory set to
50mS.
(Only appears when Pulse Inc/Dec is chosen for the Throttle Type)
Throttle Inc/Dec Pulse Delay
(High Security)
:
format of # mS. The amount of delay time before pulsing
the throttle. Increase this value for slower engine response, or decrease this value for faster engine
response.
Factory set to 250mS.
(Only appears when Pulse Inc/Dec is chosen for the Throttle Type)
Throttle Inc Rate
(Medium Security)
:
the rate the engine is signaled to increase in RPM. When using
Thomson Engine Throttle Type the setting will be shown as a gain value.
Factory set to 100 RPM/s.
Throttle Dec Rate
(Medium Security)
:
the rate the engine is signaled to decrease in RPM. When using
Thomson Engine Throttle Type the setting will be shown as a gain value.
Factory set to 100 RPM/s.
Torque Control
(High Security)
:
when Volvo is selected as the engine manufacturer this menu item
becomes active. This menu allows for enabling or disabling torque control of the engine as well as the limit
percentage of control.
Enable/Disable Torque Control:
Factory set to Disabled
Torque Limit Control:
Torque Control
Factory set to 125%
Set Throttle to Zero
(Low Security): This setting allows to zero the Thomson actuator when selected as
the Engine Throttle Type.
Throttle Direction
(Low Security): This setting allows the user to set whether the Thomson Actuator
Extends to Increase the RPM or Extends to Decrease RPM.
Factory set to Extend to Decrease.
Input / Output Menu
Digital Inputs (1-5)
(Medium Security)
:
for each of the digital inputs, the ability to select the following
parameters exists:
Digital input 1
(Medium Security)
: Factory set to Function: Disabled, Active: B-, Action: Not
Used