Section 40
33
00-02-0939
2019-06-13
Auto Stop Delay
(Medium Security)
:
this auto stop condition must remain active throughout this
delay for an auto stop to occur. If the auto stop condition is removed during this delay, the delay is
reset to zero.
Factory set to 3 seconds
ECU Stabilize Timer
(High Security)
:
on start-ups, this delay allows the ECU to stabilize and
broadcast on the CAN bus prior to actual cranking.
Factory set to 5 seconds
Crank Time
(High Security)
:
this is the length of time the crank output is turned on during cycle
cranking.
Factory set to 10 seconds
Crank Rest
(High Security)
:
this is the length of time the crank output is turned off during cycle
cranking.
Factory set to 10 seconds
Prestart Delay 1
(Low Security)
:
after a start condition has been accepted by the controller, this
delay begins timing, and the prestart #1 output turns on. When this delay expires, the output is
turned off, and the auto sequence continues.
Auto Only
(Medium Security)
: Factory set to Disabled.
Prestart Delay
(Low Security)
: Factory set to 00.00.00
Prestart Delay 2
(Low Security)
:
after a start condition has been accepted by the controller, this
delay begins timing, and the prestart #2 output turns on.
Auto Only
(Medium Security)
: Factory set to Disabled.
Prestart Delay
(Low Security)
: Factory set to 00.00.00
Prestart Delay 2 Mode
(High Security)
:
this setting determines if the prestart #2 output is active
through the crank state or only through the prestart #2 state.
Factory set to PreCrank
Spindown Timer
(Medium Security)
:
this delay begins timing when there is no call to run and the
engine speed is zero. No auto start functions will occur until this delay expires.
Factory set to 30
seconds
(Unable to set below 5 seconds)
Post Crank Lockout Setup
(Medium Security)
:
this is a setup for a delay that begins timing after
crank disconnect at startup. During this delay, the selected functions are ignored. When this delay
expires, the selected functions are armed. During the duration of this delay, the selected functions
can cycle from active to not active and not reset the delay.
Post Crank Lockout Time
(Medium Security)
: Factory set to 30 seconds
Post Crank Lockout 1
(Medium Security)
: Factory set to Low Oil Pressure
Post Crank Lockout 2
(Medium Security)
: Factory set to High Engine Temperature
Post Crank Lockout 3
(Medium Security)
: Factory set to Disabled
Post Crank Lockout 4
(High Security)
: Factory set to Disabled
Post Crank Lockout 5
(High Security)
: Factory set to Disabled
Post Warm-up Lockout Setup
(Medium Security)
:
this is a setup for a delay that begins timing
when the warm-up delay expires. During this delay, the selected functions are ignored. When this
delay expires, the selected functions are armed. During the duration of this delay, the selected
functions can cycle from active to not active and not reset the delay.
Post Warm-up Lockout Time
(Medium Security)
: Factory set to 00.00.00
Post Warm-up Lockout 1
(Medium Security)
: Factory set to Disabled