Section 40
15
00-02-0939
2019-06-13
Figure 6: Main Menu page 3
Start / Stop Timers
The Start/Stop Timers menu provides the operator the ability to add a countdown timer, scheduled
start/stop times, and an engine exercise timer. All Start/Stop timers only work when the controller is set to
auto mode. The countdown timer allows for the operator to set a desired countdown time and walk away
from the engine for a controlled shutdown when the timer expires. There are three Start/Stop Timers the
operator can choose from within this menu that allows for the specific day and hour the controller will start
and stop utilizing the internal clock. Review Start/Stop Timers under Menu Glossary section of this manual
for full list and definition of each setting.
NOTE:
Start / Stop timers work in conjunction with other Start / Stop types. The Start /
Stop times are independent of the other Auto Start methods. If the engine is already
running from another Start / Stop type when a Start / Stop timer occurs, the Start / Stop
timer is ignored. Once the engine is started by the Start / Stop timer the Auto Stop
method is ignored and will be stopped by the set Stop time.
Communication
The Communications menu allows the operator to choose the type of RS485 communications such as PVA
Gauge, Modbus or Local Display. The menu also allows for the operator to choose CAN termination and
enabling of the CAN Parameter Map. Review Communication under the Menu Glossary section of this
manual for a full list and definition of each setting.
Passcodes
The Passcodes menu is only available in the high security menu and allows the operator to see the three
level of passcodes set in the controller. The passcodes are read only in this view. Passcodes are able to
be changed from default passcode setting via PowerVision for Controllers configuration tool.