Software Release: [App: 02.09.10051.00; Config: 2.9.20024; Built in PowerVision Configuration Studio Version: 2.9.23042;
BTL: 02.09.10015.00]
Section 40
47
00-02-0939
2019-06-13
time unmonitored and then shut itself off when that time has expired or when a local key stop occurs.
Format of HH:MM:SS. Maximum countdown time is 120 hours.
Factory set to 00:00:00
NOTE:
The countdown timer is only active when starting in Auto mode. This timer will not
start counting when starting the engine in manual mode and switching to auto mode after
the engine is running.
Start / Stop Timer (1-3)
(Low Security)
:
each of the three timers contains the ability to select from the
following parameters:
Start Day
(Low Security)
: Factory set to Off
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Daily
Off
Start Time: format of HH:MM:SS (Low Security):
Factory set to 12.00.00 AM.
Stop Day
(Low Security)
: Factory set to Off
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Daily
Off
Stop Time: format of HH:MM:SS (Low Security):
Factory set to 12.00.00 AM.
Engine Exerciser
(Medium Security)
:
This feature allows the operator to set a voltage point for when the
battery voltage drops below for a given period of time the controller will provide an auto start for a defined
period of time to energize the battery using the engine alternator.
NOTE:
The exerciser is only active when the controller is in Auto mode. If the exerciser
starts the engine the exerciser is the only auto stop method to stop the engine. This holds
true with all the Start/Stop Timers.
Exercise Mode
(Medium Security)
:
Set point for the operator to enable the voltage exerciser of the
engine.
Factory set to Disabled
Low Voltage Set Point
(Medium Security)
:
Voltage the operator sets for the battery voltage to drop
below before an auto start will initiate to exercise the engine for recharging the battery.
Factory set
to 9.5V
Low Voltage Time
(Medium Security)
:
Time the operator sets for the voltage to be below the low
voltage set point before an auto start is initiated.
Factory set to 10 minutes