Post Warm-up Lockout 2
(Medium Security)
: Factory set to Disabled
Post Warm-up Lockout 3
(Medium Security)
: Factory set to Disabled
Post Warm-up Lockout 4
(High Security)
: Factory set to Disabled
Post Warm-up Lockout 5
(High Security)
: Factory set to Disabled
Bubble Lockout Setup
(Medium Security)
:
this is a setup for a delay that begins timing when the
selected functions are active. If the selected functions are removed during this delay, the delay
resets to zero. If the selected functions remain active throughout this delay, the selected action for
the parameter will occur.
Bubble Lockout Time
(Medium Security)
: Factory set to 00.00.00
Bubble Lockout 1
(Medium Security)
: Factory set to Disabled
Bubble Lockout 2
(Medium Security)
: Factory set to Disabled
Bubble Lockout 3
(Medium Security)
: Factory set to Disabled
Bubble Lockout 4
(Medium Security)
: Factory set to Disabled
Bubble Lockout 5
(Medium Security)
: Factory set to Disabled
Warnings and Shutdowns
(Low Security)
:
establish alerts for the listed parameters. When values reach
the set points in this menu the controller will show
INTERNAL FAULT
on the top left of the screen. If
nuisance faults keep occurring lower or raise the set point within this menu.
Low Oil Pressure Shutdown
(High Security)
:
a shutdown will occur when the pressure reaches
this set point.
Factory set to 10 PSI.
Low Oil Pressure Warning
(High Security)
:
an alarm will occur when the pressure reaches this
set point.
Factory set to 15 PSI.
High Engine Temp Shutdown
(Medium Security)
:
a shutdown will occur when the temperature
reaches this set point.
Factory set to 225 F.
High Engine Temp Warning
(Medium Security)
:
an alarm will occur when the temperature
reaches this set point.
Factory set to 210 F.
High Oil Temp Shutdown
(Medium Security)
:
a shutdown will occur when the temperature
reaches this set point.
Factory set to 225 F.
High Oil Temp Warning
(Medium Security)
:
an alarm will occur when the temperature reaches
this set point.
Factory set to 210 F.
Low Fuel Level Shutdown
(Medium Security)
:
a shutdown will occur when the level reaches this
set point.
Factory set to 5%.
Low Fuel Level Warning
(Medium Security)
:
an alarm will occur when the level reaches this set
point.
Factory set to 10%.
High Battery Warning
(Low Security)
:
an alarm will occur when the VDC reaches this set point.
Factory set to 16.0 VDC.
Low Battery Warning
(Low Security)
:
an alarm will occur when the VDC reaches this set point.
This setting is armed after crank disconnect upon startup.
Factory set to 8.0 VDC.
Weak Battery Warning
(Low Security)
:
an alarm will occur when the VDC reaches this set point.
Factory set to 6.0 VDC.