Micropilot FMR51, FMR52 HART
Installation
Hauser
31
6.6
Installation in bypass
1
2
2
90°
90°
A0019446
9
Installation in bypass
1
Marking for antenna alignment
2
Tank connectors
• Alighn the marker perpendicular (90°) to the tank connectors.
• Measurements can be performed through an open full bore ball valve without any
problems.
• After mounting, the housing can be turned 350° in order to facilitate access to the
display and the terminal compartment → 33.
6.6.1
Recommendations for the bypass pipe
• Metal (no plastic or enamel coating).
• Constant diameter.
• Select horn antenna as big as possible. For intermediate sizes (e.g. 95 mm (3.5 in))
select next larger antenna and adapt it mechanically (for horn antennas).
• Diameter difference between horn antenna and inner diameter of the bypass as small as
possible.
• At any transition (i.e. when using a ball valve or mending pipe segments), no gap may be
created exceeding 1 mm (0.04 in).
• In the area of the tank connections (
~
±20 cm (7.87 in)) a reduced accuracy of the
measurement has to be expected.