Operating menu
Micropilot FMR51, FMR52 HART
120
Hauser
Max. filling speed liquid
Navigation
Setup → Advanced setup → Level → Max. fill liquid
Prerequisite
Liquid
Description
Select expected maximum filling speed.
Selection
• Slow < 1cm (0.4in) /min
• Medium < 10cm (4in) /min
• Standard < 1m (40in) /min
• Fast < 2m (80in) /min
• Very fast > 2m (80in) /min
• No filter / test
Factory setting
Depending on the
Tank type
Additional information
Max. filling speed liquid
is preset by
. It can, however, be adjusted
to the process in the vessel at any time. If
is changed again at a
later point of time, it may be necessary to repeat the fine adjustment.
Max. draining speed liquid
Navigation
Setup → Advanced setup → Level → Max drain liquid
Prerequisite
Liquid
Description
Select expected maximum draining speed.
Selection
• Slow < 1cm (0.4in) /min
• Medium < 10cm (4in) /min
• Standard < 1m (40in) /min
• Fast < 2m (80in) /min
• Very fast > 2m (80in) /min
• No filter / test
Factory setting
Depending on the
Tank type
Additional information
Max. draining speed liquid (→ 120)
is preset by
however, be adjusted to the process in the vessel at any time. If
is
changed again at a later point of time, it may be necessary to repeat the fine adjustment.
Advanced process conditions
Navigation
Setup → Advanced setup → Level → Adv. conditions
Description
Specify additional process conditions (if required).
Summary of Contents for Micropilot FMR50
Page 183: ......
Page 184: ...www addresses endress com 71344017 71344017 ...