Operating menu
Micropilot FMR51, FMR52 HART
128
Hauser
Meaning of the options
•
None
The level is transmitted in the level unit without linearization.
•
Linear
The output value (volume/weight) is directly proportional to the level L. This is valid, for
example, for vertical cylinders. The following additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
: Maximum volume or weight
•
Table
The relationship between the measured level L and the output value (volume/weight) is
given by a linearization table consisting of up to 32 pairs of values "level - volume" or
"level - weight", respectively. The following additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
– For each table point:
– For each table point:
–
•
Pyramid bottom
The output value corresponds to the volume or weight in a silo with pyramid bottom.
The following additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
: Maximum volume or weight
–
•
Conical bottom
The output value corresponds to the volume or weight in a tank with conical bottom. The
following additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
: Maximum volume or weight
–
: The height of the conical part of the tank
•
Angled bottom
The output value corresponds to the volume or weight in a silo with an angled bottom.
The following additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
: Maximum volume or weight
–
•
Horizontal cylinder
The output value corresponds to the volume or weight in a horizontal cylinder. The
following additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
: Maximum volume or weight
–
•
Sphere
The output value corresponds to the volume or weight in a spherical tank. The following
additional parameters have to be specified:
–
Unit after linearization (→ 128)
–
: Maximum volume or weight
–
Unit after linearization
Navigation
Setup → Advanced setup → Linearization → Unit lineariz.
Prerequisite
Linearization type (→ 127)
≠ None
Description
Select unit of the lineaized value.