Micropilot FMR51, FMR52 HART
Operating menu
Hauser
175
Additional information
An active simulation is indicated by a diagnostic message of the
Function check (C)
category.
Value current output 1 to 2
Navigation
Expert → Diagnostics → Simulation → Value curr.out 1 to 2
Prerequisite
Current output simulation (→ 174)
On
Description
Enter current value for the simulation
User entry
3.59 to 22.5 mA
Factory setting
3.59 mA
Additional information
The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Switch output simulation
Navigation
Expert → Diagnostics → Simulation → Switch sim.
Description
Switch the simulation of the switch output on or off.
Selection
• Off
• On
Factory setting
Off
Switch status
Navigation
Expert → Diagnostics → Simulation → Switch status
Prerequisite
Switch output simulation (→ 175)
On
Description
Define the switch state to be simulated.
Selection
• Open
• Closed
Factory setting
Open
Additional information
The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.