Operating menu
Micropilot FMR51, FMR52 HART
108
Hauser
• Process vessel standard
• Process vessel with agitator
• Wave guide antenna
Factory setting
Depending on the antenna
Additional information
Depending on the antenna some of the options mentioned above may not be available or
there may be additional options.
Tube diameter
Navigation
Setup → Tube diameter
Prerequisite
=
Bypass / pipe
Description
Specify diameter of bypass or stilling well.
User entry
0 to 9.999 m
Factory setting
0 m
Medium group
Navigation
Setup → Medium group
Prerequisite
Liquid
Description
Select medium group.
Selection
• Others
• Water based (DC >= 4)
Factory setting
Others
Additional information
This parameter roughly specifies the dielectric constant (DC) of the medium. For a more
detailed definition of the DC use the
Medium property
parameter (→ 119).
The
Medium group
parameter presets the
Medium property
follows:
Medium group
Others
Unknown
Water based (DC >= 4)
DC 4 ... 7
The
Medium property
parameter can be changed at a later point of time. However,
when doing so, the
Medium group
parameter retains its value. Only the
Medium
property
parameter is relevant for the signal evaluation.
The measuring range may be reduced for small dielectric constants. For details refer
to the Technical Information (TI) of the respective device.