![Endress+Hauser Micropilot FMR50 Operating Instructions Manual Download Page 38](http://html1.mh-extra.com/html/endress-hauser/micropilot-fmr50/micropilot-fmr50_operating-instructions-manual_2407489038.webp)
Electrical connection
Micropilot FMR51, FMR52 HART
38
Hauser
4-wire: 4-20mA HART (10.4 to 48 V
DC
)
3
1
+
L+
4
2
4
...2
0
mA
H
AR
T
1
0
.4...4
8
V=
1
0
mm
Spa
re
part
7110
8xxx
2- wire
4-2
0 mA
HAR
T
[08
]
ope
n
-
L-
A
13
12
11
9
10
2
3
4
7
8
5
1
!
!
+
-
6
!
4...20 mA
≥250 Ω
A0011340
13
Terminal assignment 4-wire; 4-20mA HART (10.4 to 48 V
DC
)
1
Evaluation unit, e.g. PLC
2
HART communication resistor (≥ 250 Ω): Observe maximum load
3
Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
4
Analog display device: Observe maximum load
5
Signal cable including screening (if required), observe cable specification
6
Protective connection; do not disconnect!
7
Protective earth, observe cable specification
8
4...20mA HART (active): Terminals 3 and 4
9
Supply voltage: Terminals 1 and 2
10 Supply voltage: Observe terminal voltage, observe cable specification
11 Terminal for potential equalization
12 Cable entry for signal line
13 Cable entry for power supply
Summary of Contents for Micropilot FMR50
Page 183: ......
Page 184: ...www addresses endress com 71344017 71344017 ...