Micropilot FMR51, FMR52 HART
Operating menu
Hauser
131
Additional information
0%
H
A0013264
H
Intermediate height
The unit is defined in the
Distance unit
Table mode
Navigation
Setup → Advanced setup → Linearization → Table mode
Prerequisite
Linearization type (→ 127)
=
Table
Description
Select editing mode of the linearization table.
Selection
• Manual
• Semiautomatic
• Clear table
• Sort table
Factory setting
Manual
Additional information
Meaning of the options
•
Manual
The level and the associated linearized value are entered manually for each linearization
point.
•
Semiautomatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
•
Clear table
Deletes the existing linearization table.
•
Sort table
Rearranges the linerization points into an ascending order.
Conditions the linearization table must meet:
• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Before entering a linearization table, the values for
and
Full calibration (→ 109)
must be set correctly.
If values of the table need to be changed after the full or empty calibration have been
changed, a correct evaluation is only ensured if the existing table is deleted and the
complete table is entered again. To do so delete the existing table (
Table mode
=
Clear table
). Then enter a new table.