Micropilot FMR51, FMR52 HART
Commissioning via operating menu
Hauser
71
11.5 Configuration of the on-site display
11.5.1 Factory settings of the on-site display
Parameter
Factory setting
Format display
1 value, max. size
Value 1 display
Level linearized
Value 2 display
None
Value 3 display
None
Value 4 display
None
11.5.2 Adjustment of the on-site display
The on-site display can be adjusted in the following submenu:
Setup → Advanced setup → Display
11.6 Configuration of the current outputs
11.6.1 Factory setting of the current outputs
Current output Allocated measuring
vlaue
4mA value
20mA value
1
Level linearized
0% or the corresponding
linearized value
100% or the corresponding
linearized value
2
Distance
0
Empty calibration
1)
for devices with 2 current outputs
11.6.2 Adjustment of the current outputs
The current outputs can be adjusted in the following menus:
Basic settings
Setup → Advanced setup → Current output 1 to 2
Advanced settings
Expert → Output 1 to 2 → Current output 1 to 2
See "Description of Device Parameters", GP01014F