Operating menu
Micropilot FMR51, FMR52 HART
140
Hauser
Current span
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Current span
Description
Select current range for process variable and alarm signal.
Selection
• 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
• Fixed current
Factory setting
4...20 mA NAMUR
Additional information
Meaning of the options
Option
Current range for process
variable
Lower alarm signal level Upper alarm signal level
4...20 mA
4 to 20.5 mA
< 3.6 mA
> 21.95 mA
4...20 mA NAMUR 3.8 to 20.5 mA
< 3.6 mA
> 21.95 mA
4...20 mA US
3.9 to 20.8 mA
< 3.6 mA
> 21.95 mA
Fixed current
Constant current, defined in the
Fixed current
• In the case of an error, the output current assumes the value defined in the
Failure
mode
• If the meausred value is out of the measuring range, diagnostic message
Current
output
is issued.
In a HART multidrop loop only one device can use the analog current to transmit a
signal. For all other devices one must set:
•
Current span
=
Fixed current
•
=
4 mA
Fixed current
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Fixed current
Prerequisite
Current span (→ 140)
=
Fixed current
Description
Define constant value of the current.
User entry
4 to 22.5 mA
Factory setting
4 mA