FieldPort SWA50
Configuration and online parameterization
Hauser
51
Description of parameters on "Identification" page
Parameter
Description
Long Tag
Prerequisite
Devices from HART version 6.0
Description
Enter the name for the FieldPort.
This parameter is used for the unique identification of the FieldPort in the network
and in the plant. The parameter is used to set the burst mode and for event
notification.
User entry
Max. 32 characters from the ISO-Latin-1 character set
Factory setting
SWA50_"Serial Number"
The name must be unique in the WirelessHART network.
Device Tag
Description
Enter the name for the FieldPort.
User entry
Max. 8 characters from the Packed-ASCII character set
Factory setting
–
Descriptor
Description
Enter a description of the FieldPort such as the function or location, for example.
User entry
Max. 16 characters from the Packed-ASCII character set
Factory setting
SWA50
Date Code
Description
Enter the date of a specific event, such as the date of the last change.
User entry
dd.mm.yyyy
Message
Description
Enter a message that can be used as required.
User entry
Max. 32 characters from the Packed-ASCII character set
Factory setting
SWA50