FieldPort SWA50
Commissioning
Hauser
37
8.2.1
Commissioning via SmartBlue App
Burst messages
You can change the burst messages via WirelessHART, locally via a Commubox FXA195
using FieldCare SFE500 or via Field Xpert. You cannot change burst messages via the
SmartBlue App.
Burst message
Factory configuration
1
Every 5 minutes, the FieldPort SWA50 transmits the process values of the field device in
accordance with HART command 3.
2
Every 5 minutes, the FieldPort SWA50 transmits the diagnostic data of the field device
in accordance with HART command 48.
3
Not configured
4
Every 5 minutes, the FieldPort SWA50 transmits its own process values in accordance
with HART command 3.
5
Every 5 minutes, the FieldPort SWA50 transmits its own diagnostic data in accordance
with HART command 48.
Starting the SmartBlue App and logging in
1. Switch on the supply voltage for the FieldPort SWA50.