Commissioning
FieldPort SWA50
40
Hauser
WirelessHART configuration
Perform the following steps to ensure good communication between the FieldPort SWA50
and the WirelessHART network.
• The parameters listed in this section can be found in the "HART Configuration"
menu.
• Navigation: Root menu > System > FieldPort SWA50 > Connectivity >
WirelessHART configuration
1. Use the "Network ID" parameter to enter the identification number for the network.
2. Use the "Join Key" parameter to enter the network password. → 48
3. Use the "Connection mode" parameter to establish the connection to the network.
8.2.2
Commissioning via Field Xpert
Burst messages
Burst messages for the FieldPort SWA50 are configured in the factory. You can change the
burst messages via WirelessHART, locally via a Commubox FXA195 using FieldCare
SFE500 or via Field Xpert.
Burst message
Factory configuration
1
Every 5 minutes, the FieldPort SWA50 transmits the process values of the field device in
accordance with HART command 3.
2
Every 5 minutes, the FieldPort SWA50 transmits the diagnostic data of the field device
in accordance with HART command 48.
3
Not configured
4
Every 5 minutes, the FieldPort SWA50 transmits its own process values in accordance
with HART command 3.
5
Every 5 minutes, the FieldPort SWA50 transmits its own diagnostic data in accordance
with HART command 48.
Starting the Field Xpert and logging in
1. Switch on the supply voltage for the FieldPort SWA50.
2. Start the Field Xpert tablet PC. To do so, double-click Field Xpert on the start screen.
The following view is displayed: