Commissioning
FieldPort SWA50
42
Hauser
1. Use the "HART address field device" parameter to check the HART address of the
HART field device and adjust it if necessary. In the HART field device and in the
FieldPort SWA50, the same HART address must be used for the HART field device.
2. Use the "Communication resistor" parameter to check the setting for the HART
communication resistor. If there is no HART communication resistor outside of the
FieldPort SWA50 in the 4 to 20 mA loop, you must activate the internal HART
communication resistor. → 47
3. Use the "HART master type" parameter to check the setting for another HART master
in the HART loop. In addition to the FieldPort SWA50, only one other HART master
is permitted in the HART loop. This other HART master and the FieldPort SWA50
must not be of the same master type. → 47
WirelessHART configuration
Perform the following steps to ensure good communication between the FieldPort SWA50
and the WirelessHART network.
• The parameters listed in this section can be found in the "HART Configuration"
menu.
• Navigation: Root menu > System > FieldPort SWA50 > Connectivity >
WirelessHART configuration
1. Use the "Network ID" parameter to enter the identification number for the network.
2. Use the "Join Key" parameter to enter the network password. → 48
3. Use the "Connection mode" parameter to establish the connection to the network.