FieldPort SWA50
Commissioning
Hauser
39
3. Select device from list.
The "Device login" page is displayed.
18
Login
You can establish only
one
point-to-point connection between
one
FieldPort SWA50
and
one
smartphone or tablet.
‣
Log in. Enter
admin
as the user name and enter the initial password. The password can
be found on the nameplate.
Once the connection has been established successfully, the "Device information"
page for the selected device is displayed. → 44
Change the password after logging in for the first time. → 47
Checking and adjusting the HART configuration
Perform the following steps to ensure good communication between the FieldPort SWA50
and the connected HART field device.
• The parameters listed in this section can be found in the "HART Configuration"
menu.
• Navigation: Root menu > System > FieldPort SWA50 > Connectivity > HART
configuration
1. Use the "HART address field device" parameter to check the HART address of the
HART field device and adjust it if necessary. In the HART field device and in the
FieldPort SWA50, the same HART address must be used for the HART field device.
2. Use the "Communication resistor" parameter to check the setting for the HART
communication resistor. If there is no HART communication resistor outside of the
FieldPort SWA50 in the 4 to 20 mA loop, you must activate the internal HART
communication resistor. → 47
3. Use the "HART master type" parameter to check the setting for another HART master
in the HART loop. In addition to the FieldPort SWA50, only one other HART master
is permitted in the HART loop. This other HART master and the FieldPort SWA50