Configuration and online parameterization
FieldPort SWA50
50
Hauser
11
Configuration and online parameterization
11.1 Access options and prerequisites
11.1.1 Access options
The configuration and parameterization procedures are described based on the example of
the Hauser Asset Management Tool FieldCare SFE500.
You can access the FieldPort using FieldCare SFE500 as follows:
• Local configuration using the PC and the Hauser Commubox FXA195
USB/HART modem
• Remote configuration using the PC and the Hauser WirelessHART Fieldgate
SWG70
+
–
3
2
+
–
1
IN+
IN–
OUT+
OUT–
4
5
A0044191
24
Example: connection of the PC with FieldCare SFE500 via the Hauser Commubox FXA195
USB/HART modem for the electrical connection version "Electrical connection for 2-wire HART field
devices with passive current output"
1
Supply voltage or PLC with active current input or transmitter with active current input
2
Electronic insert SWA50 (internal communication resistor enabled)
3
2-wire field device 4 to 20 mA-HART
4
Hauser Commubox FXA195 USB/HART modem
5
PC with FieldCare SFE500
11.1.2 Required settings in FieldCare
In FieldCare, activate the "Prefer FDT 1.2.1 scanning" option.
Path: FieldCare > Extras > Options > "Scanning" tab > "Scan Result" section
11.2 Identification
This page allows you to configure the parameters that are required to identify the
FieldPort. The factory settings are displayed in the individual fields.
Navigation
Online parameterization > Identification