FieldPort SWA50
Configuration and online parameterization
Hauser
63
Description of parameters for "Event Notification", "Event" tab
Parameter
Description
Event Notification
Control Code
Description
Enable and disable the event notification mode.
Selection
• Off: the event notification mode is disabled. The entry fields are grayed out and
write-protected.
• On: the event notification mode is enabled. It is possible to enter data.
Factory setting
Off
Additional information
The event notification parameters are written to the FieldPort after the "Apply"
button is clicked.
Device Index
Prerequisite
Event notification: on
Description
Select the device for which the event notification parameters are active.
Selection
• SWA50
• Connected field device
Factory setting
SWA50
Event Notification Retry
Time
Prerequisite
Event notification: on
Description
Enter the time between two attempts to transmit event notification. The
transmission attempt is repeated until the FieldPort receives confirmation of
receipt.
User entry
• 00:00:01
• 00:00:02
• 00:00:04
• 00:00:08
• 00:00:16
• 00:00:32
• From 00:01:00, any time can be specified
Factory setting
00:30:00
Maximum Update Time
Prerequisite
Event notification: on
Description
Enter the maximum time that is used if no event change occurs. If no event occurs,
the FieldPort sends event notification after this period of time. If an event
notification occurs during this time, the timer is restarted.
User entry
• 00:00:01
• 00:00:02
• 00:00:04
• 00:00:08
• 00:00:16
• 00:00:32
• From 00:01:00, any time can be specified
Factory setting
00:30:00
Event Debounce Interval Prerequisite
Event notification: on
Description
Enter the time that an event must last before the event notification is sent.