11.7 Event Notification
General information
Event notification is a special application similar to the burst mode. An event notification
is sent as soon as there are changes in the device configuration or device status, regardless
of whether data are already being sent by burst mode commands. You can use the status
included in the device status byte, the extended device status byte and in command 48 for
event notification. You can define a specific number of bits that will trigger event
notification.
Event notifications have a lower priority than burst modes. Event notifications are given a
time stamp indicating when a notification was triggered for the first time. You can define
up to 2 different event notifications.
"Event Notification Control Code" page and "Event Notification Control Code 1" and
"Event Notification Control Code 2" pages
The "Event Notification Control Code" page provides an overview of the event notifications
that are configured. You can define 2 different event notifications using the "Event
Notification Control Code 1" and "Event Notification Control Code 2" pages.
You can also configure event notifications offline. The event notifications take effect as
soon as the FieldPort is connected to the network.
Navigation
• Online parameterization > Application Settings > Event Notification > Event Notification
1
Online parameterization > Application Settings > Event Notification > Event Notification
1
• Online parameterization > Application Settings > Event Notification > Event Notification
2
Online parameterization > Application Settings > Event Notification > Event Notification
2
Configuring event notification
1. Open the page for configuring an event notification, e.g. the
Event Notification
Control Code 1
page.
2. On the "Event" tab, select the
On
option for the
"Event Notification Control Code"
parameter.
The gray fields become white. It is possible to enter data.
3. For the
Device Index
parameter, select either the FieldPort SWA50 or the connected
HART field device.
4. Configure the remaining parameters on the "Event" tab.