FieldPort SWA50
Description of SmartBlue app for SWA50
Hauser
47
"Bluetooth configuration" page
Navigation: Root menu > System > FieldPort SWA50 > Connectivity > Bluetooth
configuration
This page is used to configure the Bluetooth connection and to carry out firmware updates
for the FieldPort SWA50.
Page
Description
Reduce radio transmit power
Enable and disable a reduction in the transmission power of the SWA50.
Options
• Yes: The transmission power of the SWA50 is reduced.
• No: The transmission power of the SWA50 is not reduced.
Factory setting
No
Change Bluetooth password
Change password. To change it, you must enter the user name, the
current password and the new password.
Factory setting
• User name: admin
• The password can be found on the nameplate.
Firmware update
"HART configuration" page
Navigation: Root menu > System > FieldPort SWA50 > Connectivity > HART configuration
This page is used to configure the HART parameters for the FieldPort SWA50. In addition,
you can configure the HART address of the connected HART field device.
Parameter
Description
HART address field device
Configure the HART address of the HART field device.
User entry
0 to 63
Factory setting
0
HART master type
Select HART master type.
Options
• Primary master
• Secondary master
Factory setting
Secondary master
Communication resistor
Select installation site of HART communication resistor.
Options
• External: Use external communication resistor provided by customer
between IN+ terminal and supply voltage.
• Internal: Use internal communication resistor of SWA50.
Factory setting
External
HART address SWA50
Configure the HART address of the SWA50 for slave access to SWA50.
User entry
0 to 63
Factory setting
15
"HART Info" page
Navigation: Root menu > System > FieldPort SWA50 > Connectivity > HART info