Appendix
Ecograph T, RSG35
120
Hauser
Description
Contains setup for the selected relay.
x = place holder for selected relay.
Operating mode
Navigation
Expert → Outputs → Relay x → Operating mode
Direct access code: 330000-00x
Examples: Relay 1:330000-000; Relay 6: 330000-005
Description
Relay function:
NC contact: The relay is closed in its quiescent state (maximum safety).
NO contact: The relay is open in its quiescent state.
Options
Closing, Opening
Factory setting
Closing
Identifier
Navigation
Expert → Outputs → Relay x → Identifier
Direct access code: 330001-00x
Examples: Relay 1:330001-000; Relay 6: 330001-005
Description
Presettable relay identifier.
User entry
Text (max. 16 characters)
Factory setting
Relay x
16.1.4 "Communication" submenu
Set-up required if you are using the USB, RS232, RS485 or Ethernet interface of the unit
(PC operation, serial data read-out, modem operation, etc.).
The various interfaces can be operated in parallel.
Timeout
Navigation
Expert → Communication → Timeout
Direct access code: 150200-000
Description
Timeout is modifiable between 1 and 99 seconds. 0 seconds means that the functionality
is inactivated.
User entry
0 to 99s