Ecograph T, RSG35
Appendix
Hauser
151
Set point
Navigation
Expert → Application → Limits → Limit x → Set point
Direct access code: 450003-0xx
Examples: Set point 1: 450003-000; Set point 30: 450003-029
Description
Limit value in the set process unit, e.g. in °C, m³/h.
User entry
Number (max. 10 digits)
Factory setting
0
Hysteresis (abs.)
Navigation
Expert → Application → Limits → Limit x → Hysteresis (abs.)
Direct access code: 450004-0xx
Examples: Set point 1: 450004-000; Set point 30: 450004-029
Description
The alarm condition is only canceled when the signal has changed into the normal
operation range by the preset value.
User entry
Number (max. 8 digits)
Factory setting
0
Time delay
Navigation
Expert → Application → Limits → Limit x → Time delay
Direct access code: 450005-0xx
Examples: Set point 1: 450005-000; Set point 30: 450005-029
Description
In order to be interpreted as an alarm the signal must exceed or undercut the preset value
by at least the time set up.
User entry
0 to 99999 s
Factory setting
0 s
Switches
Navigation
Expert → Application → Limits → Limit x → Switches
Direct access code: 450006-0xx
Examples: Set point 1: 450006-000; Set point 30: 450006-029