Contains settings for displaying/acknowledging messages. Examples of messages include:
messages triggered by set-points; messages triggered by a digital input; error messages;
etc.
Acknowledging messages
Navigation
Expert → System → Messages → Acknowledging messages
Direct access code: 100040-000
Description
The time the message is acknowledged can be saved in the events list.
Options
Do not save, Save
Factory setting
Do not save
Switches relay
Navigation
Expert → System → Messages → Switches relay
Direct access code: 100042-000
Description
A relay can be switched as soon as a message that has to be confirmed is displayed (e.g.
on/off message, device errors etc.).
The relay assumes the initial status as soon as all messages have been confirmed.
Options
Not used, Relay x
All the available relays are displayed
Factory setting
Not used
"Screen saver" submenu
Navigation
Expert → System → Screensaver
Description
To increase the life span of the LCDs the backlight can be switched off (= screen saver).
Screen saver
Navigation
Expert → System → Screen saver → Screen saver
Direct access code: 160000-000
Description
"Switched off": LCD is always switched on.
“Switch on for x min.”: display goes dark after x minutes. All other functions remain in
operation. Press an operating key: Illumination is switched back on.
"Switch daily": Enter time span.