Ecograph T, RSG35
Appendix
Hauser
101
Description
Factor, that when multiplied by the input signal results in the required physical value.
Example: 1 pulse equals 5 m
3
-> enter "5".
Only visible if signal = pulse counter.
User entry
Number, max. 8 digits
Factory setting
1
Decimal point
Navigation
Expert → Inputs → Universal inputs → Universal input x → Decimal point
Direct access code: 220005-0xx
Examples: Universal input 1: 220005-000; Universal input 12: 220005-011
Description
Number of places after decimal point for the display.
Only visible if signal ≠ switched off.
Options
None, One (X.Y), Two (X.YY), Three (X.YYY), Four (X.YYYY), Five (X.YYYYY)
Factory setting
One (X.Y)
Lower frequency
Navigation
Expert → Inputs → Universal inputs → Universal input x → Lower frequency
Direct access code: 220018-0xx
Examples: Universal input 1: 220018-000; Universal input 12: 220018-011
Description
Configure the lower frequency that corresponds to the start of the measuring range.
Only visible if signal = frequency input.
User entry
0 to 12500 (Hz)
Factory setting
5.0 (Hz)
Range start
Navigation
Expert → Inputs → Universal inputs → Universal input x → Range start
Direct access code: 220006-0xx
Examples: Universal input 1: 220006-000; Universal input 12: 220006-011