Ecograph T, RSG35
Appendix
Hauser
113
Options
No, Digital input x
Factory setting
No
Function
Navigation
Expert → Inputs → Digital inputs → Digital input x → Function
Direct access code: 250000-00x
Examples: Digital input 1: 250000-000; Digital input 6: 250000-005
Description
Select the required function: Digital inputs are High active; this means the described effect
is achieved by a high input.
Low = -3 to +5V
High = +12 to +30V.
Options
Switched off, control input, on/off event, pulse counter, operational time, event+operation
time, quantity from time, Modbus slave (option)
Factory setting
Switched off
Function
Navigation
Expert → Inputs → Digital inputs → Digital input x → Function
Direct access code: 250014-00x
Examples: Digital input 1: 250014-000; Digital input 6: 250014-005
Description
Specifies how the data from the fieldbus is interpreted/processed.
Only visible if function = Modbus Slave
Options
Switched off, Control input, On/off event, Pulse counter, Operational time, Event
+operation time, Quantity from time
Factory setting
Switched off
Channel ident.
Navigation
Expert → Inputs → Digital inputs → Digital input x → Channel ident.
Direct access code: 250001-00x
Examples: Digital input 1: 250001-000; Digital input 6: 250001-005
Description
Measurement point name (e.g. "Pump") or description of the function of this input (e.g.
"Fault message").
Only visible if function ≠ switched off.
User entry
Text (max. 16 characters)