Ecograph T, RSG35
Appendix
Hauser
145
Calc. factor
Navigation
Expert → Application → Maths → Maths x → Totalization → Calc. factor
Direct access code: 400054-00x
Examples: Maths 1: 400054-000; Maths 4: 400054-003
Description
Factor for calculating the integrated value (e.g. the transmitter delivers l/s -> totalization
base = second -> engineering unit required is m³ -> enter factor 0.001)
Only visible if totalization = yes.
User entry
Number (max. 8 digits)
Factory setting
1.0
Totalizer
Navigation
Expert → Application → Maths → Maths x → Totalization → Totalizer
Direct access code: 400055-00x
Examples: Maths 1: 400055-000; Maths 4: 400055-003
Description
Initial setting for the totalizer. Useful when continuing measurements recorded to date
with an (electro)-mechanical counter.
Only visible if totalization = yes.
User entry
Number (max. 15 digits)
Factory setting
0
"Fault mode" submenu
Navigation
Expert → Application → Maths → Maths x → Fault mode
Description
Contains settings that specify how this channel is to behave in the event of an error (e.g. if
an input channel has a cable open circuit or there is division by 0).
On error
Navigation
Expert → Application → Maths → Maths x→ Fault mode → On error
Direct access code: 400060-00x
Examples: Maths 1: 400060-000; Maths 4: 400060-003
Description
Configure what value the device should continue working with (for calculations) if the
measured value is not valid (e.g. cable open circuit).
Options
Invalid calculation, Error value