EM15 User’s Manual
5. Description of Function Codes
35
b0-05
Selection of auxiliary frequency Y range
Default
0
Setting
Range
0
Relative to maximum frequency
1
Relative to main frequency X
b0-06
Range of auxiliary frequency Y
Default
100%
Setting Range
0%~150%
If X and Y operation is used, b0-05 and b0-06 are used to set the adjustment range of theauxiliary frequency source.
You can set the auxiliary frequency to be relative to either maximum frequency or main frequency X. If relative to
main frequency X, the setting range of the auxiliary frequency Y varies according to the main frequency X.
b0-07
Frequency source logic selection
Default
0
Setting
Range
Unit's digit: Frequency source selection.
0
Only by main frequency source X(b0-03)
1
X and Y calculation (calculation result determined by ten's digit)
2
Switchover between X and Y
3
Switchover between X and "X and Y calculation"
4
Switchover between Y and "X and Y calculation"
Ten's digit: X and Y calculation relationship
0
X+Y
1
X-Y
2
Maximum of them
3
Minimum of them
It is used to select the frequency setting channel. Frequency setting can be realized by the main frequency source X
and auxiliary frequency source Y operation.
Diagram 5-1 Target frequency setting
If the frequency source involves X and Y operation, you can set the frequency offset in b0-08 for superposition to the
X and Y operation result, flexibly satisfying various requirements.
b0-08
Encoder knob frequency change unit
Default
0
Setting
0
1Hz