EM15 User’s Manual
Appendix II
153
Code
Parameter Name
Functional description
Default
Property
d6-00 Carrier frequency
0.5kHz~16.0 kHz
Model
dependent
☆
d6-01
DPWM switchover
frequency upper limit
5.00Hz~15.00 Hz
8.00 Hz
★
d6-02 PWM modulation mode
0: Asynchronous modulation
1: Synchronous modulation
0
★
d6-03
Carrier frequency
adjustment with
temperature
0: No
1: Yes
1
☆
d6-04
Dead zone compensation
mode selection
0: No compensation
1: Compensation mode 1
2: Compensation mode 2
1
☆
d6-05 Random PWM depth
0: Random PWM invalid
1~10: Random PWM carrier frequency depth
0
☆
d6-06
Current detected
compensation
0~100
0
★
d6-07 SVC mode selection
1: SVC mode 1
2: SVC mode 2
2
☆
Group U0: Standard Monitoring Parameters
U0-00 Running frequency
0.00~300.00 Hz (b0-11 = 2)
-
●
U0-01 Setting frequency
0.00~3000.0 Hz (b0-11 = 1)
-
●
U0-02 DC Bus voltage
0.0~3000.0 V
-
●
U0-03 Output voltage
0V~1140 V
-
●
U0-04 Output current
0.00A~655.35 A (Frequency inverter power ≤ 55 kW)
0.0A~6553.5 A (Frequencyinverter power > 55 kW)
-
●
U0-05 Output power
0~32767
-
●
U0-06 Output torque
-200.0%~200.0%
-
●
U0-07 DI state
-0~32767
-
●
U0-08 DO state
0~1023
-
●
U0-09 AI1 voltage
-
-
●
U0-10 AI2 voltage
-
-
●
U0-11 AI3 voltage
-
-
●
U0-14 Load speed display
0~65535
-
●
U0-15 PID setting
0~65535
-
●
U0-16 PID feedback
0~65535
-
●
U0-17 PLC stage
-
-
●
U0-18 Input pulse frequency
0.00kHz ~100.00 kHz
-
●
U0-19
Feedback speed,
unit:0.01Hz
-3000.0Hz~3000.0 Hz
-300.00Hz~300.00 Hz
-
●
U0-20 Remaining running time
0.0min~6500.0 min
-
●
U0-21
AI1 voltage before
correction
0.00V~10.57 V
-
●
U0-22
AI2 voltage before
correction
0.00V~10.57 V
-
●
U0-23
AI3 voltage before
correction
-10.57V~10.57 V
-
●
U0-24 Linear speed
0.0min~65535m/min
-
●