Appendix II
EM15 User’s Manual
142
Code
Parameter Name
Functional description
Default
Property
bb-32
Fault protection action
selection 1
Unit's digit: Motor overload, Err11.
0: Free stop
1: Stop according to the stop mode
2: Continue to run
Ten's digit: Power input phase loss, Err12.
Same as unit's digit
Hundred's digit: Power output phase loss, Err13.
Same as unit's digit
Thousand's digit: External equipment fault, Err15.
Same as unit's digit
Ten thousand's digit: Communication fault, Err16.
Same as unit's digit
00000
☆
bb-33
Fault protection action
selection 2
Unit's digit: Encoder/PG card fault, Err20.
0: Free stop
Ten's digit: EEPROM read-write fault, Err21.
0: Free stop
1: Stop according to the stop mode
Hundred's digit : Reserved
Thousand's digit: Motor Overheat, Err25.
Same as unit's digit in bb-32
Ten thousand's digit: Running time reached, Err26.
Same as unit's digit in bb-32
00000
☆
bb-34
Fault protection action
selection 3
Unit's digit: User-defined fault 1,Err27.
Same as unit's digit in bb-32
Ten's digit: User-defined fault 2,Err28.
Same as unit's digit in bb-32
Hundred's
digit: Accumulative
power-on time
reached,Err29.
Same as unit's digit in bb-32
Thousand's digit: Off load, Err30.
0: Free stop
1: Stop according to the stop mode
2: reduce to 7% of rated motor frequency and continue
running. If the load recovers and it will auto regain to
setting frequency.
Ten thousand's digit: PID feedback lost during running,
Err31.
Same as unit's digit in bb-32
00000
☆
bb-35
Fault protection action
selection 4
Unit's digit: Speed deviation too large, Err42
Same as unit's digit in bb-32
Ten's digit: Motor over-speed, Err43.
Same as unit's digit in bb-32
Hundred's digit: Initial position fault, Err51.
Same as unit's digit in bb-32
00000
☆
bb-37
Frequency selection for
continuing to run of fault
0: Current running frequency
1: Set frequency
2: Frequency upper limit
0
☆