EM15 User’s Manual
5. Description of Function Codes
101
U0-00 ~ U0-31 are the monitoring parameters in the running and stop state defined by b9-02 and b9-03.
U0-00
Running frequency
Display Range
0.00~300.00 Hz (b0-11 = 2)
U0-01
Setting frequency
Display Range
0.00~3000.0 Hz (b0-11 = 1)
These two parameters display the absolute value of theoretical running frequency and set frequency. For the actual
output frequency of the frequency inverter, see U0-19.
U0-02
DC Bus voltage
Display Range
0.0~3000.0 V
It displays the frequency inverter's DC bus voltage.
U0-03
Output voltage
Display Range
0V~1140 V
It displays the frequency inverter's output voltage in the running state.
U0-04
Output current
Display Range
0.00A~655.35 A (Power ≤ 55 kW)
0.0A~6553.5 A (Power > 55 kW)
It displays the frequency inverter's output current in the running state.
U0-05
Output power
Display Range
0~32767
It displays the frequency inverter's output power in the running state.
U0-06
Output torque
Display Range
-200.0%~200.0%
It displays the frequency inverter's output torque in the running state.
U0-07
DI state
Display Range
-0~32767
It displays the present state of DI terminals. After the value is converted into a binary number, each bit
corresponds to a DI. "1" indicates high level signal, and "0" indicates low level signal. The corresponding
relationship between bits and DIx is described in the following table.
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
DI1
DI2
DI3
DI4
DI5
HDI
DI7
DI8
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
DI9
DI10
VDI1
VDI2
VDI3
VDI4
VDI5
U0-08
DO state
Display Range
0~1023
It indicates the present state of DO terminals. After the value is converted into a binary number, each bit
corresponds to a DO terminal. "1" indicates high level signal, and "0" indicates low level signal. The
corresponding relationship between bits and DOx is described in the following table.
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
DO3
Relay 1 Relay 2
DO1
DO2
VDO1 VDO2 VDO3
Bit8
Bit9
Bit10
Bit11
Bit12
Bit13
Bit14
Bit15
VDO4
VDO4
U0-14
Load speed display
Display Range
0~1023
For more details, see the description of b9-06.