Unidrive SPM User Guide
283
Issue Number: 3 www.controltechniques.com
PSAVE.Er
Power down save parameters in the EEPROM are corrupt
37
Indicates that the power was removed when power down save parameters were being saved.
The drive will revert back to the power down parameter set that was last saved successfully.
Perform a user save (Pr
xx.00
to 1000 or 1001 and reset the drive) or power down the drive normally to ensure this trip does or occur
the next time the drive is powered up.
rS
Failure to measure resistance during autotune or when starting in open loop vector mode 0 or 3
33
Check motor power connection continuity
SAVE.Er
User save parameters in the EEPROM are corrupt
36
Indicates that the power was removed when user parameters were being saved.
The drive will revert back to the user parameter set that was last saved successfully.
Perform a user save (Pr
xx.00
to 1000 or 1001 and reset the drive) to ensure this trip does or occur the next time the drive is
powered up.
SCL
Drive RS485 serial comms loss to remote keypad
30
Reinstall the cable between the drive and keypad
Check cable for damage
Replace cable
Replace keypad
SLX.dF
Solutions Module slot X trip: Solutions Module type installed in slot X changed
204,209,214
Save parameters and reset
SL3.dF
Building automation interface slot trip
214,214
Module typed changed
Trip
Diagnosis