188
Unidrive SPM User Guide
www.controltechniques.com Issue Number: 3
*For more information, refer to section 13.21.5
Stop modes
on
page 257.
**For more information, refer to section 13.21.6
Line power supply loss
modes
on page 258.
***For more information, refer to section 13.21.7
Start / stop logic
modes
on page 259.
****For more information, refer to section 13.21.8
Catch a spinning
motor
on page 260.
*****The drive thermal model system normally controls the fan speed,
however the fan can be forced to operate at full speed if this parameter
is set to 1. When this is set to 1 the fan remains at full speed until 10s
after this parameter is set to zero. Note that the fan willl only run at full
speed if the drive is not in a UU condition.
Parameter
Range(
Ú
)
Default(
Ö
)
Type
OL
CL
OL
VT
SV
6.01
Stop mode
COASt (0), rP (1),
rP.dcl (2), dcl (3),
td.dcl (4), diSAbLE (5)
COASt (0), rP (1),
no.rP (2)
rP (1)
no.rP (2)
RW Txt
US
6.03
Line power supply loss mode
diS (0), StoP (1), ridE.th (2)
diS (0)
RW Txt
US
6.04
Start / stop logic select
0 to 4
4
RW Uni
US
6.06
Injection braking level
0 to 150.0%
100.0%
RW Uni
RA
US
6.07
Injection braking time
0.0 to 25.0s
1.0
RW Uni
US
6.08
Hold zero speed
OFF (0) or On (1)
OFF (0)
On (1)
RW Bit
US
6.09
Catch a spinning motor
{
0.33
}
0 to 3
0 to 1
0
1
RW Uni
US
6.12
Enable stop key
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.13
Enable forward / reverse key {
0.28
}
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.15
Drive enable
OFF (0) or On (1)
On (1)
RW Bit
US
6.16
Electricity cost per kWh
0.0 to 600.0 currency units per kWh
0
RW Uni
US
6.17
Reset energy meter
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.18
Time between filter changes
0 to 30,000 hrs
0
RW Uni
US
6.19
Filter change required /
change done
OFF (0) or On (1)
OFF (0)
RW Bit
PT
6.20
Powered-up time: years.days
0 to 9.364 years.days
RW Uni
NC PT
6.21
Powered-up time:
hours.minutes
0 to 23.59 hours.minutes
RW Uni
NC PT
6.22
Run time: years.days
0 to 9.364 years.days
RO Uni
NC PT PS
6.23
Run time: hours.minutes
0 to 23.59 hours.minutes
RO Uni
NC PT PS
6.24
Energy meter: MWh
±999.9 MWh
RO Bi
NC PT PS
6.25
Energy meter: kWh
±99.99 kWh
RO Bi
NC PT PS
6.26
Running cost
±32,000
RO Bi
NC PT
6.27
Time before filter change due
0 to 30,000 hrs
RO Uni
NC PT PS
6.28
Select clock for trip log time
sampling
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.29
Hardware enable
OFF (0) or On (1)
RO Bit
NC PT
6.30
Sequencing bit: Run forward
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.31
Sequencing bit: Jog forward
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.32
Sequencing bit: Run reverse
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.33
Sequencing bit: Forward /
reverse
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.34
Sequencing bit: Run
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.35
Forward limit switch
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.36
Reverse limit switch
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.37
Sequencing bit: Jog reverse
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.39
Sequencing bit: Not stop
OFF (0) or On (1)
OFF (0)
RW Bit
NC
6.40
Enable sequencer latching
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.41
Drive event flags
0 to 65,535
0
RW Uni
NC
6.42
Control word
0 to 32,767
0
RW Uni
NC
6.43
Control word enable
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.44
Active supply
OFF (0) or On (1)
RO Bit
NC PT
6.45
Force cooling fan to run at full
speed
*****
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.46
Nominal low voltage supply
48V to 96V
48
RW Uni
PT US
6.47
Disable line power supply /
phase loss detection from
input rectifier
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.48
Line powersupply loss ride
through detection level
0 to DC_VOLTAGE_SET_MAX V
200V drive: 205, 400V drive: 410,
575V drive: 540, 690V drive: 540
RW Uni
RA
US
6.49
Disable multi-module drive
module number storing on trip
OFF (0) or On (1)
OFF (0)
RW Bit
US
6.50
Drive comms state
drv (0), SLot 1(1), SLot 2 (2), SLot 3 (3)
RO Txt
NC PT
6.51
External rectifier not active
OFF (0) or On (1)
OFF (0)
RW Bit
RW Read / Write
RO
Read only
Uni
Unipolar
Bi
Bi-polar
Bit
Bit parameter
Txt
Text string
FI
Filtered
DE
Destination
NC
Not copied
RA
Rating dependent
PT
Protected
US
User save
PS