Unidrive SPM User Guide
www.controltechniques.com Issue Number: 3
Table 11-5 SMARTCARD status indications
C.rtg
SMARTCARD trip: The voltage and/or current rating of the source and destination drives are different
186
Drive rating dependent parameters (parameters with the RA coding) are likely to have different values and ranges with drives of
different voltage and current ratings. Parameters with this attribute will not be transferred to the destination drive by SMARTCARDs
when the rating of the destination drive is different from the source drive and the file is a parameter file. However, with software
V01.09.00 and later drive rating dependent parameters will be transferred if only the current rating is different and the file is a
differences from default type file.
Press the red
reset button
Drive rating parameters are:
The above parameters will be set to their default values.
C.Typ
SMARTCARD trip: SMARTCARD parameter set not compatible with drive
187
Press the red
reset button
Ensure destination drive type is the same as the source parameter file drive type
Table 11-4 Trip conditions
Trip
Diagnosis
Parameter
Function
2.08
Standard ramp voltage
4.05
/
6
/
7
,
21.27/8/9
Current limits
4.24
User current maximum scaling
5.07
,
21.07
Motor rated current
5.09
,
21.09
Motor rated voltage
5.10
,
21.10
Rated power factor
5.17
,
21.12
Stator resistance
5.18
Switching frequency
5.23
,
21.13
Voltage offset
5.24
,
21.14
Transient inductance
5.25
,
21.24
Stator inductance
6.06
DC injection braking current
6.48
Line power supply loss ride through detection level
Lower display
Description
Lower display
Description
boot
A parameter set is being transferred from the
SMARTCARD to the drive during power-up. For further
information, please refer to section 11.2.4
Booting up
from the SMARTCARD on every power up (Pr 11.42 =
boot (4))
.
cArd
The drive is writing a parameter set to the SMARTCARD
during power-up.
For further information, please refer to section
11.2.3
Auto saving parameter changes (Pr 11.42 = Auto
(3))
.