If Pr
8.39
is set to OFF (0), then the setting of Pr
1.14
automatically
changes the operation of digital inputs T28 and T29 by configuring the
destination parameters Pr
8.25
and Pr
8.26
. To allow Pr
8.25
and Pr
8.26
to be changed manually by the user, the automatic set-up must be
disabled by setting Pr
8.39
to 1.
If Pr
8.39
is 0 and Pr
1.14
is changed, then a drive reset is required
before the function of terminal T28 or T29 will become active.
* Setting Pr
1.15
to 9 enables the Preset reference scan timer. With the
scan timer enabled analog 1 and preset references 2 to 8 are selected
automatically in turn. Pr
1.16
defines the time between each change.
** Jog forward can only be selected when the drive is in either the ready
(rdy), inhibit (inh) or trip states.
Reference modes
Pr
1.14
, Pr
1.15
and Pr
8.39
Braking modes
Pr
2.04
and Pr
2.08
S ramps
Pr
2.06
and Pr
2.07
Torque modes
Pr
4.08
and Pr
4.11
Stop modes
Pr
6.01
, Pr
6.06
, Pr
6.07
and Pr
6.08
Main loss modes
Pr
6.03
, Pr
6.48
, Pr
4.13
and Pr
4.14
Start/stop logic modes
Pr
6.04
and Pr
6.40
Catch a spinning motor
Pr
6.09
and Pr
5.40
Position loop modes
Pr
13.10
Fast disable
Pr
6.29
1.14
Reference selector
RW
Txt
NC
US
Ú
A1.A2 (0), A1.Pr (2), A2.Pr (2),
Pr (3), PAd (4), Prc (5)
Ö
A1.A2 (0)
1.15
Preset reference selector
RW
Uni
NC
US
Ú
0 to 9
Ö
0
8.39
T28 and T29 auto-selection disable
RW
Bit
US
Ú
OFF (0) or On (1)
Ö
OFF (0)
Table 13-7 Active reference
Pr 1.14
Pr 1.15
Digital Input T28
Digital Input T29
Pr 1.49
Pr 1.50
Active Reference
State
Function
State
Function
A1.A2
(0)
0 or 1
0
Local Remote
Jog forward**
1
1
Analog input 1
1
2
1
Analog input 2
2 to 8
No function
1 or 2
2 to 8
Preset reference 2 to 8
9 *
0
Local Remote
1
1
Analog input 1
1
2
1
Analog input 2
No function
1 or 2
2 to 8
Preset reference 2 to 8
A1.Pr
(1)
0
0
Preset select bit 0
0
Preset select bit 1
1
1
Analog input 1
1
2
Preset reference 2
0
1
3
Preset reference 3
1
4
Preset reference 4
1
No function
No function
1
Analog input 1
2 to 8
2 to 8
Preset reference 2 to 8
9 *
1
Analog input 1
2 to 8
Preset reference 2 to 8
A2.Pr
(2)
0
0
Preset select bit 0
0
Preset select bit 1
2
1
Analog input 2
1
2
Preset reference 2
0
1
3
Preset reference 3
1
4
Preset reference 4
1
No function
No function
1
Analog input 2
2 to 8
2 to 8
Preset reference 2 to 8
9 *
1
Analog input 2
2 to 8
Preset reference 2 to 8
Pr
(3)
0
0
Preset select bit 0
0
Preset select bit 1
3
1
Preset reference 1
1
2
Preset reference 2
0
1
3
Preset reference 3
1
4
Preset reference 4
1 to 8
No function
No function
1 to 8
Preset reference 1 to 8
9 *
1 to 8
Preset reference 1 to 8
PAd
(4)
No function
No function
4
Keypad reference
Prc
(5)
No function
No function
5
Precision reference