SLX.Er
Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202,207,212
Automation (I/O Expansion) module category
Check value in Pr
15/16
/
17.50
. The following table lists the possible error codes for the SM-I/O Plus, SM-I/O Lite, SM-I/O Timer, SM-
I/O PELV, SM-I/O 120V and SM-I/O 24V Protected. See the
Diagnostics
section in the relevant Solutions Module User Guide for
more information.
SLX.Er
Solutions Module slot X trip: Solutions Module in slot X has detected a fault
202,207,212
Fieldbus module category
Check value in Pr
15
/
16
/
17.50
. The following table lists the possible error codes for the Fieldbus modules. See the
Diagnostics
section in the relevant Solutions Module User Guide for more information.
Trip
Diagnosis
Error code
Module
Reason for fault
0
All
No errors
1
All
Digital output overload
2
SM-I/O Lite, SM-I/O Timer
Analog input 1 current input too high (>22mA) or too low (<3mA)
SM-I/O PELV, SM-I/O 24V Protected
Digital input overload
3
SM-I/O PELV, SM-I/O 24V Protected
Analog input 1 current input too low (<3mA)
SM-I/O 24V Protected
Communications error
4
SM-I/O PELV
User power supply absent
5
SM-I/O Timer
Real time clock communication error
74
All
Module over temperature
Error code
Module
Trip Description
0
All
No trip
52
SM-PROFIBUS-DP, SM-Interbus,
SM-DeviceNet, SM-CANOpen
User control word trip
58
SM-LON
Incorrect non-volatile storage
61
SM-PROFIBUS-DP, SM-Interbus,
SM-DeviceNet, SM-CANOpen, SM-
SERCOS, SM-LON
Configuration error
64
SM-DeviceNet
Expected packet rate timeout
65
SM-PROFIBUS-DP, SM-Interbus,
SM-DeviceNet, SM-CANOpen, SM-
SERCOS, SM-LON
Network loss
66
SM-PROFIBUS-DP
Critical link failure
SM-CAN, SM-DeviceNet, SM-CANOpen
Bus off error
69
SM-CAN
No acknowledgement
70
All (except SM-Ethernet and SM-LON)
Flash transfer error
SM-Ethernet, SM-LON
No valid menu data available for the module from the drive
74
All
Solutions module over temperature
75
SM-Ethernet
The drive is not responding
76
SM-Ethernet
The Modbus connection has timed out
80
All (except SM-SERCOS)
Inter-option communications error
81
All (except SM-SERCOS)
Communications error to slot 1
82
All (except SM-SERCOS)
Communications error to slot 2
83
All (except SM-SERCOS)
Communications error to slot 3
84
SM-Ethernet
Memory allocation error
85
SM-Ethernet
File system error
86
SM-Ethernet
Configuration file error
87
SM-Ethernet
Language file error
98
All
Internal watchdog error
99
All
Internal software error