Table 14-22 Unidrive SPMC/U 400V input current, fuse and cable size rating
Table 14-23 Unidrive SPMC/U 690V input current, fuse and cable size ratings
N
The cable sizes noted in Table 14-20, Table 14-21, Table 14-22 and Table 14-23 are typical cable sizes based on UL508C and IEC60364-5-52:2001.
Maximum cable sizes are 2 x 240mm
2
or 2 x 400kcmil per pole. The user will have to decide what size of cable to use in any given application based
on the local wiring regulations. Use of high temperature cables that are thinner than those stated in the typical cable chart maybe possible, contact the
supplier of the drive for advice.
14.1.21 Line reactor ratings
Table 14-24 400V input line reactor ratings
*May represent a more economic solution where operating temperature and cooling requirements are observed.
Table 14-25 400V dual input line reactor ratings
Table 14-26 690V input line reactor ratings
Table 14-27 690V dual input line reactor ratings
N
The INLX1X parallel line reactors have been designed to work in conjunction with the Unidrive SPMC/U, allowing one reactor to be used with the dual
rectifier model or two separate rectifier units.
Model
Maximum
input
current
Typical
DC
output
current
Semiconductor fuse in
series with HRC fuse
Typical cable size
HRC IEC
Class gG UL
class J
Semi-
conductor
IEC class aR
AC input
DC output cable
Cable
installation
method
A
A
A
A
mm
2
AWG
mm
2
AWG
SPMC/U1402
344
379
450
400
2 x 120
2 x 4/0
2 x 120
2 x 4/0
B1 or C
SPMC/U2402
2 x 312
2 x 345
450
400
2 x 120
2 x 4/0
2 x 120
2 x 4/0
B1 or C
Model
Maximum
input
current
Typical
DC
output
current
Semiconductor fuse in
series with HRC fuse
Typical cable size
HRC IEC
Class gG UL
class J
Semi-
conductor
IEC class aR
AC input
DC output cable
Cable
installation
method
A
A
A
A
mm
2
AWG
mm
2
AWG
SPMC/U1601
195
209
250
250
2 x 70
2 x 2/0
2 x 120
2 x 4/0
B2
SPMC/U2602
2 x 173
2 x 185
250
250
2 x 70
2 x 2/0
2 x 120
2 x 4/0
B2
NOTE
Model
Current
A
Inductance
μ
H
Overall
width (W)
mm
Overall
depth (D)
mm
Overall
height (H)
mm
Weight
kg
Max ambient
temp
°C
Min
airflow
m/s
Quantity
required
Part No
INL 401
245
63
240
190
225
32
50
1
1
4401-0181
INL 402
339
44
276
200
225
36
50
1
1
4401-0182
INL 401W*
245
63
255
235
200
27
40
3
1
4401-0208
INL 402W*
339
44
255
235
200
27
40
3
1
4401-0209
Model
Current
A
Inductance
μ
H
Overall
width (W)
mm
Overall
depth (D)
mm
Overall
height (H)
mm
Weight
kg
Max ambient
temp
°C
Min
airflow
m/s
Quantity
required
Part No.
INL411
2 x 245
2 x 31.5
320
220
360
55
50
1
1
4401-0206
INL412
2 x 339
2 x 22
320
220
360
55
50
1
1
4401-0207
Model
Current
A
Inductance
μ
H
Overall
width (W)
mm
Overall
depth (D)
mm
Overall
height (H)
mm
Weight
kg
Max ambient
temp
°C
Min
airflow
m/s
Quantity
required
Part No.
INL 601
145
178
240
190
225
33
50
1
1
4401-0183
INL 602
192
133
276
200
225
36
50
1
1
4401-0184
Model
Current
A
Inductance
μ
H
Overall
width (W)
mm
Overall
depth (D)
mm
Overall
height (H)
mm
Weight
kg
Max ambient
temp
°C
Min
airflow
m/s
Quantity
required
Part No.
INL 611
2 x 145
2 x 89
320
220
360
40
50
1
1
4401-0190
INL 612
2 x 192
2 x 66.5
320
220
360
55
50
1
1
4401-0191
NOTE