Table 4-5: Data Logging Parameters
Parameter
Description
Default
P590
Log Interval
The logging interval is the period over which the
parameter-to-be-logged is sampled every five
seconds and then averaged at the end. The averaged
value is then logged.
An interval value of 15 minutes logs the averaged
value at 15-minute intervals, which equates to 50
days elapsed time.
15 minutes
P591
Fast Log (Fast
log mode)
If the parameter-to-be-logged value is higher than a
user-entered value (P591), the 3493 automatically
moves to a fast log mode.
The parameter-to-be-logged is then logged once
every minute until the logged value is less than P591.
Fast logged values are tagged for easy identification
when examining logged data.
0
P592
Data Overwrite
After the logging memory is full, there is a choice to
continue data logging and overwrite the oldest data
(On) or to stop data logging (Off).
On
P593
Low Mem Alarm An alarm can be raised to indicate when the unused
memory falls to below a user-defined percentage
(P593). See
for selecting if this alarm is
indicated by a relay output, driving the output
current to a set level, or both.
When the memory is full, logged data is either
overwritten or the data logging stops, as determined
by parameter P592.
Parameter D846 shows the percentage of free
memory remaining for data logging.
0%
Related information
Data logging screens
Starting, stopping and resetting the logger
Using the logging wizard for data logging of level measurements
Using the logging wizard for data logging of flow measurements
Getting started
Reference Manual
January 2021
00809-0100-4841
86
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...