(shield) connected to terminal 3 (marked with earth/ground symbol) on the control unit.
The cable screen (shield) should be left unconnected at the transmitter end unless there is
a terminal specifically provided for this purpose.
Cable runs should be separate from any high voltage or mains cables to avoid crosstalk or
interference.
shows the layout of the control unit terminals. All terminal blocks are suitable
for wires 14 to 26 AWG (0.5 to 1.5 mm
2
), except the mains terminals which are suitable for
wires 10 AWG (2.5 mm
2
). Insulation should be stripped back
¼
-in. (7 mm).
Figure 3-5: Connection Terminals Layout (for Mains-Powered Wall-Mount Unit)
The dc powered unit has a slightly different layout – terminals 31 and 32 replace terminals
28 and 29.
Transmitter connections are made on the left side of the terminals enclosure. Connecting
the intrinsically safe earth/ground (terminal 30) to a high integrity earth/ground point is
recommended if the transmitter connected to terminals 1 and 2 is in a hazardous area
Note
In intrinsically safe systems, apparatus connected to the Rosemount 3490 Series Control
Unit must not be supplied from a voltage greater than 250 V r.m.s. or 250 Vdc.
Installation
Reference Manual
January 2021
00809-0100-4841
24
Emerson.com/Rosemount
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...