![Emerson Rosemount 3490 Series Reference Manual Download Page 23](http://html.mh-extra.com/html/emerson/rosemount-3490-series/rosemount-3490-series_reference-manual_2400788023.webp)
Dimensional drawings
Making electrical connections on wall-mount units
3.3.3
Mounting the NEMA 4X-rated wall mount version
Procedure
1. Mount the unit on a suitable wall or structure using the fixing points.
2. Make the electrical connections.
Related information
Installation guidelines for the NEMA 4X-rated wall mount version
Dimensional drawings
Making electrical connections on wall-mount units
3.4
Electrical installation
WARNING
It is the responsibility of the installer to:
Refer to safety data and electrical specifications in
Specifications and reference data
Refer to the certifications and control drawings in
.
Check and obtain any work permits required before applying power to the unit.
Observe all local regulations and approval requirements.
Ensure the wiring is suitable for the load current.
Ensure the wiring insulation is suitable for the voltage, temperature, and environment of
the installation.
Drill holes in the base of the NEMA
®
4X-rated control unit for fitting cable glands.
Ensure suitable cable glands or conduit connections are used when wiring to the control
unit to maintain enclosure integrity.
Never remove or modify the mechanical barriers separating the terminal area from the
main enclosure and separating the transmitter input terminals from other terminals.
3.4.1
Making electrical connections on wall-mount units
Note
Use only 167 °F (75 °C) copper conductors for field wiring.
All field wiring connections are accessible by removing the lower terminal cover, which is
secured by two screws on the IP-rated version and by four screws on the NEMA 4X rated
version.
The cabling between the Rosemount 3490 Series Control Unit (“control unit”) and a
transmitter should be a screened (shielded), twisted-pair type with the cable screen
Reference Manual
Installation
00809-0100-4841
January 2021
Emerson.com/Rosemount
23
Summary of Contents for Rosemount 3490 Series
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual January 2021 00809 0100 4841 8 Emerson com Rosemount ...
Page 16: ...Control unit overview Reference Manual January 2021 00809 0100 4841 16 Emerson com Rosemount ...
Page 36: ...Installation Reference Manual January 2021 00809 0100 4841 36 Emerson com Rosemount ...
Page 134: ...Getting started Reference Manual January 2021 00809 0100 4841 134 Emerson com Rosemount ...
Page 184: ...Additional features Reference Manual January 2021 00809 0100 4841 184 Emerson com Rosemount ...
Page 189: ...Reference Manual 00809 0100 4841 January 2021 Emerson com Rosemount 189 ...